| All your needs for the CLASSIC 816: |
 |
|
| |
Specifications
|
Applications
|
 |
-
Flow, level, interface and temperature
|
| |
Material of Construction - Sensor
|
 |
-
316 Stainless Steel, standard
-
Pressure Seal-Sensor; Highly Saturated Nitrile
|
| |
Process Connection - Threaded
|
 |
-
1" MNPT (Male National Pipe Thread)
|
| |
Pressure Rating - Retractable Packing Gland
|
 |
-
Low Pressure; 50 psi
-
Low Pressure c/w Security Chain; 125 psi
-
Medium Pressure; 500 psi
|
| |
Insertion 'U' Lengths
|
 |
-
Imperial:
Custom lengths are available from 2.5" to 120"
-
Metric:
Custom lengths are available from 6.4 cm to 305 cm
|
| |
Sensor Operating Temperature Range - Continuous Use
|
 |
-
-40°C to +160°C (-40°F to +320°F)
|
| |
| |
Electronics Operating Temperature Range - Continuous Use
|
 |
-
-55°C to +65°C (-67°F to +149°F).
For temperatures above 75°C (+167°F) remote mounting of electronics is
required.
|
| |
Input Power
|
 |
-
12-24 VDC; 115-230 VAC, 50-60 Hz
-
Universal Power Input
-
Power Consumption:
Maximum 4.8 watts (fully configured)
|
| |
Electronics - Standard Features
|
 |
-
100% digital design. All electronics are environmentally sealed
-
4-20 mA output scaled to flow range
-
Intelligent user interface with push-button setup and constant display of
operation
-
Temperature compensation
-
Automated redundant self-test diagnostics
-
MODBUS support via RS-485 communications*
-
Easy setup: no mechanical jumpers or trim pots
-
Incrementally adjustable heater power (5% steps) with automatic over-range
protection
-
Two independent relays
-
Temperature Mode*: Process temperature may be displayed/graphed in Flow/Level
mode
-
4 adjustable independent switch point timers
-
Display Panel Lock-Out*
-
Start-up Bypass Timer
* Requires Kayden RCM Software.
Available on request.
|
| |
Outputs
|
 |
|
| |
Communications
|
 |
-
RS-485 using Kayden's Remote Control & Monitoring Software (RCMS) or other
MODBUS compatible software
|
| |
Switch Point Range
|
 |
-
Water-based Liquids:
0.01 to 3.00 ft./sec. (0.003 to .9 meters/sec)
-
Hydrocarbon-based Liquids:
0.01 to 5.0 ft./sec. (0.003 to 1.50 meters/sec)
-
Gases:
0.25 to 200 SFPS (0.08 to 60 SMPS)
Standard condition: 21ºC (70ºF) at 14.7 psi (1 atm)
|
| |
Accuracy
|
 |
-
Flow Service:
±1.0% of set point velocity over operating range of ±50ºF (±28ºC)
-
Level Service:
±0.25 inches (±0.64 cm)
|
| |
Response Time
|
 |
-
Approximately 0.5 to 30 seconds.
|
| |
Agency Approvals
|
 |
Local (Sensor) Enclosure:
-
CSA - Flameproof
Class I, Div.1, Groups B, C and D; Ex d IIB + H2;
AEx d IIB + H2
(Class I, Zone 1, Group IIB + H2)
- T3; Enclosure Type 4 / IP55
- Single Seal approved per ANSI / ISA 12.27.01-2003
-
FM - Flameproof
- Class I, Division 1, Groups B, C & D
- Temperature Codes: T2D (Ta=75ºC), T3 (Ta=65ºC)
- Class I, Zone 1, AEx d IIB + H2
- Type 4 / IP55
-
Blind Cover standard
-
Glass Lens Cover optional
-
Enclosure - copper-free aluminum; Powder Coated Polyester TGIC; O-ring on
cover.
|
 |
Remote Electronics Enclosure - Optional:
-
CSA - Flameproof
- Class I, Groups B, C & D; Ex d IIB + H2
- AEx d IIB + H2
(Class I, Zone 1, Groups IIB + H2)
- Temperature Code: T3
-
FM - Flameproof
- Class I, Division 1, Groups B, C & D
- Temperature Codes: T2D (Ta=75ºC), T3 (Ta=65ºC)
- Class I, Zone 1, AEx d IIB + H2
- Type 4 / IP55
-
Blind Cover standard
-
Glass Lens Cover optional
-
One Electronics Module per enclosure; Larger enclosures available
-
Enclosure - copper-free aluminum; Powder Coated Polyester TGIC; O-ring on
cover.
|
| |
Kayden RCMSTM
- Optional (Remote Control & Monitoring Software)
|
 |
-
Operated via a personal computer locally or from a remote control center
-
Monitor operating status
-
Adjust set points 1 & 2
-
Adjust relay modes
-
Modify heater settings to optimize response time
-
Lock or unlock the Display Panel to protect the settings
-
Load or save user settings
-
Visualize the actions of the process via the graphical display
-
Many other adjustable features
|
| |
| Configure |
| |
 |