| All your needs for the BASIC 423: |
 |
|
| |
Specifications
|
Applications
|
 |
|
| |
Material of Construction - Sensor
|
 |
-
316L Stainless Steel,All-Welded,standard
|
| |
Process Connection - Flanged
|
 |
-
Raised Face and RTJ (Ring-Type Joint)
-
Flange size and weight range from 1" 150# to 10" 2500#
|
| |
Insertion 'U' Lengths
|
 |
-
Imperial:
Custom lengths are available from 2.5" to 244"
-
Metric:
Custom lengths are available from 6.0cm to 620cm
|
| |
Sensor Operating Temperature Range - Continuous Use
|
 |
-
-55° C to +200° C (-67° F to +392° F)
|
| |
Operating Pressure - Sensor
|
 |
-
Maximum working pressure to rating of flange
-
MWP derated with temperature
|
| |
Electronics Operating Temperature Range - Continuous Use
|
 |
-
-55° C to +75° C (-67° F to +167° F).
For temperatures above 75° C (+167° F) remote mounting of electronics enclosure
is required.
|
| |
Input Power
|
 |
-
12-24 VDC; 115-230 VAC, 50-60 Hz
-
Universal Power Input
-
Power Consumption:
Maximum 6 watts
|
| |
Electronics - Standard Features
|
 |
-
Microprocessor based electronics, environmentally sealed
-
Intelligent user interface, constant display of operation (Flow/Level)
-
Temperature compensation
-
Automated redundant self-test diagnostics
-
MODBUS support via RS-485 communications*
-
Variable heater power
* Requires KAYDEN RCM Software.
Available on request.
|
| |
Outputs
|
 |
-
MODBUS registers via RS-485
-
Single SPST sealed relay contact rated @ 5 amps resistive 230 VAC or 24 VDC
|
| |
Communications
|
 |
-
RS-485 using MODBUS compatible software
|
| |
Flow Switch Service Range
|
 |
-
Water-based Liquids:
0.01 to 3.25 fps (0.003 to 0.99 mps)
-
Hydrocarbon-based Liquids:
0.01 to 5.4 fps (0.003 to 1.64 mps)
-
Gases:
0.25 to 195 sfps (0.076 to 59 smps)
SStandard condition: 21º C (70º F) 1 ATM
-
Other Fluids:
Contact Kayden
-
Lower Flow Rates:
The BASIC is available for low flow rate applications with the In-Line 430
& 432 models
|
| |
Level Switch Service Range
|
 |
-
Accuracy:
±0.25 inch (±0.64 cm)
-
Repeatability:
±0.125 inch (±0.32 cm)
-
Repeatability:
±0.05ºF (±0.025ºC)
|
| |
Set Point Accuracy
|
 |
-
Liquids:
±5% of reading (or ±0.04 sfps; ±0.012 smps), whichever is larger
-
Gases:
±5% of reading (or ±2 sfps; ±0.6 smps), whichever is larger
-
Repeatability:
±0.5% of reading
1% of full signal range at constant process conditions
|
| |
Response Rates
|
 |
-
0.5 to 30 seconds. Actual response time can vary due to fluid type, direction
of change and specific application.
|
| |
Agency Approvals
|
 |
Local (Sensor) Enclosure:
-
FM - Flameproof
- Class I, Division 1, Groups C & D
- Temperature codes: T2D (Ta=75ºC), T3 (Ta=65ºC)
- Class I, Zone 1, AEx d IIB
- Type 4/IP55
-
Blind cover standard
-
Lens cover optional
-
Enclosure epoxy coated with O-ring on 8-pin cover
-
Security locking screw for cover
|
 |
Remote Electronics Enclosures - Optional:
-
FM - Flameproof
- Class I, Division 1, Groups C & D
- Temperature codes: T2D (Ta=75ºC), T3 (Ta=65ºC)
- Class I, Zone 1, AEx d IIB
- Type 4/IP55
-
Blind cover standard
-
Lens cover optional
-
One electronics module per enclosure
-
Enclosure epoxy coated with O-ring on 8-pin cover
|
| |
| Configure |
| |
 |