Kayden Instruments Corporate
ID: Psw:
partners | 

Support FAQ

 
Q1   The indicator lights do not come on.
A1   Check for incoming power with a low impedance volt-meter. Using a high impedance voltmeter, especially on AC volts can sometimes be misleading. You require 12 to 26 VDC or 110 to 240 VAC to operate our switches.
 
Q2   The FAULT indicator is on and flashes 2 different displays.
A2   There is a fault with your switch. One display shows the software revision in 2 digit HEX code on the left side, and the MODBUS address on the right side. The second display shows the actual fault as follows:

50% - Heater shorted
55% - Heater open
60% - Heated RTD shorted
65% - Heated RTD open
70% - Reference RTD shorted
75% - Reference RTD open
 
Q3   How can I manually check the probe?
A3   Use an OHM METER and check these resistances. These values are approximate and may vary depending on ambient temperature.

RED to RED  50 Ohms
BLUE to BLUE  0 Ohms
BLACK to BLACK  0 Ohms
BLUE to YELLOW  1100 Ohms
BLACK to WHITE  1100 Ohms
RED to any other lead  Infinite
BLUE to BLACK  Infinite

Any other readings indicate that the probe may be defective. The probe is not field repairable.
 
Q4   Why I get any 4-20 mA loop current from my CLASSIC switch?
A4   The CLASSIC switch requires an external loop supply in order to operate. This can be supplied from any 12 to 24 VDC supply as this port is isolated from the CLASSIC circuitry.
 
Q5   My 4-20 mA loop reads differently from my Thermal Signal display.
A5   Using the RCMS software, check the settings for the 4-20 mA loop. It may be set to respond to the process temperature and not the Thermal Delta.
 
Q6   The keyboard on my CLASSIC does not function.
A6   Using the RCMS software, check to make sure that the keyboard has not been locked out. If it has, enable the keyboard, or configure the switch from the software. Usually, the keyboard has been locked to prevent others from changing critical settings.
 
Q7   Why don't the relays switch immediately when a set point has been reached?
A7   There may have been a time delay set for the set point.
 
Q8   Why does the BYPASS light come on when I power up the switch?
A8   The BYPASS timer has been set.
 
Q9   Why does the FAULT light not go out as soon as a fault has been cleared?
A9   The FAULT timer has been set.
 
Q10   I want my relays to be energized whenever the switch is functioning properly. Can I set this?
A10   Yes. You can do this through software or from the keyboard on the CLASSIC. To select FAIL SAFE mode, press the SET button until Relay 1 is selected. Press the RIGHT arrow so that the 70% to 100% LEDs are illuminated. The relay will now be energized until the Relay 1 set point is reached. Do the same thing for Relay 2. The function of the relay contacts will change, ie: the NC contacts now become NO and the NO contacts become NC when the switch is powered up.
 
Q11   My question is not in this list.
A11  
See also: http://kayden.com/media/documents/guides/Troubleshooting Sec 7 from CLASSIC 800 Manual Aug 2009-HiRes.pdf
or
http://kayden.com/media/documents/guides/Troubleshooting Sec 7 from BASIC+ 400 Manual Aug 2009-HiRes.pdf
or
Contact Kayden at techsupport@kayden.com