SCA Adapters

Serial Communications Adapter

The Kayden SCA-321 is a port-powered 2-channel RS-232 to RS-485 converter. It converts the TD and RD RS-232 lines to balanced half-duplex RS-485 signals. The unit is powered from the RS-232 data and handshake lines regardless of whether the lines are high or low. The Kayden SCA-321 has a DB-9 female connector on the RS-232 side and a detachable terminal block connector on the RS-485 side.
 
 
sca adapter Kayden SCA Adapter
Kayden's SCA (Serial Communications Adapter) is an RS-232/485 converter for MODBUS communication protocol. The SCA derives power from the host's serial port.
Part Number: A15-321
communication cable Kayden Communication Cable
Kayden's Communication Cable is used to connect the SCA to the switch. Standard Lengths: 4, 8 & 10 feet.
Part Number: A05-CC-0004 4 feet (1.23 m)
Part Number: A05-CC-0008 8 feet (2.44 m)
Part Number: A05-CC-0010 10 feet (3.05 m)
sca adapter
RS-232 End View
 
adapter diagram
Power Requirements
Requires at least two RS-232 output handshake lines for power.
RS-232 Side
Connector: DB-9 female
Signals: Passes through pins 3 (TD) and 2 (RD). Pins 7 (RTS) and 8 (CTS) are tied together. Pins 4 (DTR), 6 (DSR), and 1 (CD) are tied together.
RS-485 Side
Connector: 3 pin terminal block
Signals: Half-duplex two-wire operation only. Automatic control circuit enables driver only when transmitting. Receiver is disabled when transmitting to prevent echo back to RS-232 device. Can transmit up to 4000 feet at 19,200 baud.
Dimensions
  2.75" x 1.25" x 0.6"
7cm x 3.2cm x 1.5cm
No handshaking is required to control the RS-485 driver. The handshake lines are required but only to provide power to the converter. The RS-485 driver is automatically enabled during each spacing state on the RS-232 side. During the marking or idle state, the RS-485 driver is disabled and the data lines are held in the marking state by pull-up and pull-down resistors.

The SCA-321 has an internal connection to prevent data transmitted from the RS-232 port from being echoed back to the RS-232 port. The SCA-321 is used as a two wire (half duplex) RS-485 converter with a third conductor to be used as signal ground. Using a common signal ground ensures that the common mode voltage between devices falls within the specifications of RS-485. This is especially important for networked devices with opto-isolated RS-485 interfaces.

Using the SCA-321 to communicate to most RS-485 devices does not usually require any termination. Termination is used to match impedance of a node to the impedance of the transmission line being used. When impedances are mismatched, the transmitted signal is not completely absorbed by the load and a portion is reflected back into the transmission line. This reflected signal can cause communication errors especially on long cable runs using a high data rate. If termination is required, the SCA-321 only supports AC coupled terminators. One terminator should be installed on each end of a straight cable run. A typical AC termination is a 120 Ohm resistor and a 0.1 uF capacitor in series between 485(+) and 485(-).